13
TABLE 2
SUCTION LINE LENGTH/SIZE VS CAPACITY MULTIPLIER (R-410A)
NOTES:
*Standard line size
Using suction line larger than shown in chart will result in poor oil return and is not recommended.
5/8 [15.9] Opt.
3/4* [19] Std.
5/8 [15.9] Opt.
3/4* [19] Std.
5/8 [15.9] Opt.
3/4* [19] Std.
7/8 [22.2] Opt.
5/8 [15.9] Opt.
7/8* [22.2] Std.
3/4 [19] Opt.
7/8* [22.2] Opt.
7/8 [22.2] Opt.
1 1/8* [28.6] Std.
7/8 [22.2] Opt.
1 1/8* [28.6] Std.
Unit Size
Suction Line Connection Size
Suction Line Run - Feet [m]
3/4”
[19] I.D.
3/4”
[19] I.D.
3/4”
[19] I.D.
7/8”
[22.2] I.D.
7/8”
[22.2] I.D.
7/8”
[22.2] I.D.
7/8”
[22.2] I.D.
1 1/2 Ton 2 Ton 2 1/2 Ton 3 Ton 3 1/2 Ton 4 Ton 5 Ton
Optional
25’ [7.6] Standard
Optional
Optional
50’ [15.24] Standard
Optional
Optional
100’ [30.5] Standard
Optional
Optional
150’ [45.7] Standard
Optional
1.00 1.00 1.00 1.00 1.00 1.00 1.00
1.00 1.00 1.00 1.00 1.00 1.00 1.00
——1.00 ——
0.98 0.98 0.96 0.98 0.99 0.99 0.99
0.99 0.99 0.98 0.99 0.99 0.99 0.99
——0.99 ——
0.95 0.95 0.94 0.96 0.96 0.96 0.97
0.96 0.96 0.96 0.97 0.98 0.98 0.98
——0.97 ——
0.92 0.92 0.91 0.94 0.94 0.95 0.94
0.93 0.94 0.93 0.95 0.96 0.96 0.97
——0.95 ——

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem 13 Series and is the answer not in the manual?

Rheem 13 Series Specifications

General IconGeneral
RefrigerantR-410A
Voltage208/230V
Compressor TypeScroll
Cooling Capacity18, 000-60, 000 BTU/h
Heating Capacity18, 000-60, 000 BTU/h
StagesSingle

Related product manuals