10.0 DIAGNOSTICS AND TROUBLESHOOTING
10.2 Status and Diagnostic Codes
Descriptions of the EcoNet
TM
2-Stage Control diagnostic codes are provided below:
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
Status/Possible Cause - Trouble-
shooting Information
29 - High Pressure Control Open
The Outdoor Control detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or lter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
29L - Active Protection High Pressure Control Trip HPC has opened 3 times in the same cooling
operation, the Outdoor Control has locked out
the compressor to protect it. Outdoor Control
alternately ashes L and 29
48 - Open Run Circuit or No Compressor Current Check to ensure power to compressor is
correct
Check capacitor
49 - Compressor Current with No Call For Cooling Check for welded contactor contacts
Check for shorted wires
84 - Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or high
outdoor ambient temperature
Check unit placement - If the outdoor units is
in a high temperature area, wait until the am-
bient temperature drops and check sensor
reading.
Replace the sensor
Check if sensor is installed correctly on Out-
door Control
93 - Internal Control Fault
The control is not functioning properly
Check Outdoor Control for proper system
operation
Replace Outdoor Control
d1 - No Shared Data Replace memory card with correct system
information.
FLASHING
Diagnostics

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem A17 Series and is the answer not in the manual?

Rheem A17 Series Specifications

General IconGeneral
BrandRheem
ModelA17 Series
CategoryHeat Pump
LanguageEnglish

Related product manuals