17
Tubing
4.5 Line Set Installation (cont.)
4.0 INSTALLATION
4.5.2 Relative Location of Indoor and Outdoor Units
4.5.2.1 Outdoor Unit Level or Near Level to Indoor Coil Line Set
ST-A1219-01-01
REFERENCE TABLE 2 FOR
MAXIMUM LENGTH LIMITATIONS
IDEALLY, LINE SET SLOPES AWAY
FROM OUTDOOR UNIT. VERIFY
SUB-COOLING PRIOR TO EXPANSION
DEVICE, INSULATED LIQUID LINE IN
UNCONDITIONED SPACE.
INSULATED VAPOR LINE FULL LENGTH
Figure 3
For applications with the outdoor unit and indoor
unit on the same level the following is required:
Insulated liquid line in unconditioned space only.
Vapor line should slope toward the indoor unit.
(Reference Figure 3)
Follow the proper line sizing, maximum linear
and equivalent length, charging requirements,
and oil level adjustments spelled out in this
document.
Verify at least 5°F [2.8°C] sub-cooling at the
indoor unit prior to expansion device.