18.3 Electrical Checks Flow Chart
No
No
No
No
Yes
Yes
Yes
Yes
O
utdoor Unit
Running?
7-Segment display lit?
Flashing Mode Character
Alternating “C” and “##” (Code)
SEE PANEL COVER OR
OTHER DOCUMENTATION
FOR FAULT CODE
TROUBLESHOOTING.
Control in Lockout Mode.
Check fault history and refer to
Diagnostic Chart.
Note: For solid comm LED, check
comm wiring, term/bus switches at
ICC and AH ctrls.
R
efer to panel cover/documentation
f
or Fault Code Troubleshooting.
C
heck fault history for other faults.
Check control voltage (R and C)
to control
Waiting for Anti-S.C. Delay to clear
T
hermostat call
For cooling, no cooling
No
Yes
Y1 LED lit?
No call received.
24V Systems: Check thermostat,
control wiring
Comm Systems: Check comm.
wiring, T-Stat
41