EasyManua.ls Logo

Rheem RHPD Series - Page 36

Rheem RHPD Series
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
ELECTRICAL DATA - RHPDZT SERIES
102ACF 102ACG 102ACH 102ADF 102ADG 102ADH 102AYF 102AYG
102AYH
Unit Information
Unit Operating Voltage Range 187-253 187-253 187-253 414-506 414-506 414-506 517-632 517-632
517-632
Volts 208/230 208/230 208/230 460 460 460 575 575
575
Phase 3 3 3 3 3 3 3 3
3
Hz 60 60 60 60 60 60 60 60
60
Minimum Circuit Ampacity 48 50 53 23 24 25 17 18
18
Minimum Overcurrent Protection Device
Size
60 60 70 30 30 30 20 25
25
Maximum Overcurrent Protection Device
Size
70 70 80 30 35 35 25 25
25
Compressor Motor
No. 1 1 1 1 1 1 1 1
1
Volts 200/230 200/230 200/230 460 460 460 575 575
575
Phase 3 3 3 3 3 3 3 3
3
RPM 3450 3450 3450 3450 3450 3450 3450 3450
3450
HP, Compressor 1 7 1/2 7 1/2 7 1/2 7 1/2 7 1/2 7 1/2 7 1/2 7 1/2
7 1/2
Amps (RLA), Comp. 1 28.8 28.8 28.8 12.5 12.5 12.5 9.7 9.7
9.7
Amps (LRA), Comp. 1 191 191 191 100 100 100 70 70 70
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
Condenser Motor
No. 2 2 2 2 2 2 2 2
2
Volts 208/230 208/230 208/230 460 460 460 575 575
575
Phase 1 1 1 1 1 1 1 1
1
HP 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
1/2
Amps (FLA, each) 2.5 2.5 2.5 1.5 1.5 1.5 1.1 1.1
1.1
Amps (LRA, each) 5.6 5.6 5.6 3.1 3.1 3.1 1.5 1.5
1.5
Evaporator Fan
No. 1 1 1 1 1 1 1 1
1
Volts 208/230 208/230 208/230 460 460 460 575 575
575
Phase 3 3 3 3 3 3 3 3
3
HP 2 3 3 2 3 3 2 3
3
Amps (FLA, each) 7 8.9 12 3.5 4.4 6 2.5 3.5
3.5
Amps (LRA, each)
47 74.5 74.5 24 38.1 38.1 19 20 20
ELECTRICAL DATA

Related product manuals