ELECTRICAL DATA - RHPDZT SERIES
120ACF 120ACG 120ACH 120ADF 120ADG 120ADH 120AYF 120AYG 120AYH
Unit Information
Unit Operating Voltage Range 187-253 187-253 187-253 414-506 414-506 414-506 517-632 517-632 517-632
Volts 208/230 208/230 208/230 460 460 460 575 575 575
Phase 3 3 3 3 3 3 3 3 3
Hz 60 60 60 60 60 60 60 60 60
Minimum Circuit Ampacity 54 57 58 26 27 28 19 20 20
Minimum Overcurrent Protection Device
Size
70 70 70 30 35 35 25 25 25
Maximum Overcurrent Protection Device
Size
80 80 90 40 40 40 25 30 30
Compressor Motor
No. 1 1 1 1 1 1 1 1 1
Volts 200/230 200/230 200/230 460 460 460 575 575 575
Phase 3 3 3 3 3 3 3 3 3
RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450
HP, Compressor 1 10 10 10 10 10 10 10 10 10
Amps (RLA), Comp. 1 32.6 32.6 32.6 14.8 14.8 14.8 11.1 11.1 11.1
Amps (LRA), Comp. 1 240 240 240 130 130 130 93.7 93.7 93.7
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
Condenser Motor
No. 2 2 2 2 2 2 2 2 2
Volts 208/230 208/230 208/230 460 460 460 575 575 575
Phase 1 1 1 1 1 1 1 1 1
HP 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Amps (FLA, each) 2.5 2.5 2.5 1.5 1.5 1.5 1.1 1.1 1.1
Amps (LRA, each) 5.6 5.6 5.6 3.1 3.1 3.1 1.5 1.5 1.5
Evaporator Fan
No. 1 1 1 1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460 575 575 575
Phase 3 3 3 3 3 3 3 3 3
HP 2 3 3 2 3 3 2 3 3
Amps (FLA, each) 7.7 10.4 12 3.9 5.2 6 2.5 3.5 3.5
Amps (LRA, each) 47 74.5 74.5 24 38.1 38.1 19 20 20
ELECTRICAL DATA