2. Quick Reference Guide For R-410A
R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-22.
Ensure that servicing equipment is designed to operate with R-410A.
R-410A refrigerant cylinders are pink.
R-410A, as with other HFC’s is only compatible with POE oils.
Vacuum pumps will not remove moisture from POE oil.
R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R-410A refrig-
erant cylinders had a dip tube. These cylinders should be kept upright for equipment charging.
Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid
charging of the equipment.
Do not install a suction line filter drier in the liquid line.
A liquid line filter drier is standard on every unit.
Desiccant (drying agent) must be compatible for POE oils and R-410A.
3. Evaporator Coil/ Expansion Device
The expansion device is specifically designed to operate with R-410A. DO NOT use an R-22.
The existing evaporator must be replaced with the factory specified device evaporator
specifically designed for R-410A.
4. Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High Side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
!
CAUTION
R-410A SYSTEMS OPERATE AT HIGHER PRESSURE THAN R-22 SYSTEMS. DO NOT
USE R-22 SERVICE EQUIPMENT OR COMPONENTS ON R-410A EQUIPMENT.
6