29
While scroll compressors usually do not require
crankcase heaters, there are instances when a
heater should be added� Refrigerant migration
during the off cycle can result in a noisy start up�
Add a crankcase heater to minimize refrigeration
migration, and to help eliminate any start up noise
or bearing “wash out�”
NOTE: The installation of a crankcase heater is
recommended if the system charge exceeds the
values in the table below� The 5 ton model comes
with a crankcase heater factory installed�
All heaters are located on the lower half of the
compressor shell� Its purpose is to drive refrigerant
from the compressor shell during long cycles,
thus preventing damage to the oompressor during
start-up�
At initial start-up or after extended shutdown
periods, make sure the heater is energized for at
least 12 hours before the compressor is started�
(Disconnect switch on and wall thermostat off�)
Compressor Crankcase Heat (CCH)
High- and Low-Pressure Controls (HPC and LPC)
Standard on RP14: These controls keep the
compressor from operating in pressure ranges
which can cause damage to the compressor� Both
controls are in the low-voltage control circuit�
The high-pressure control (HPC) is an automatic-
reset which opens near 610 PSIG and closes near
420 PSIG�
The low-pressure control (LPC) is an automatic-
reset which opens near 15 PSIG and closes near
40 PSIG�
CAUTION: The compressor has
an internal overload protector� Under some
conditions, it can take up to 2 hours for this
overload to reset� Make sure overload has had
time to reset before condemning the compressor
Start components are not usually required with
the scroll compressors used in heat pumps, but
are available for special cases and where start
components are desirable to reduce light dimming�
Hard start components are available through
Prostock�
Hard-Start Components
COMPONENTS AND CONTROLS
MAXIMUM SYSTEM CHARGE VALUES: (-)PNL
Charge Limit
Model Compressor Without
Size*Model Number Crankcase Heater*
-018 ZP16K5E-PFV-13R 9.6 lbs.
-024 ZP21K6E-PFV-130 9.6 lbs.
-030 ZP25K5E-PFV-13R 9.6 lbs.
-036 ZP31K5E-PFV-13
R9
.6 lbs.
-048 ZP42K5E-PFV-13R 12 lbs.
-060 ZP49K6E-PFV-130 12 lbs.
Components