EasyManua.ls Logo

Riello Array AR 500 SE - Page 73

Riello Array AR 500 SE
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
73
RECYCLING AND DISPOSAL
73
APPENDIX
APPENDIX
Menu
Par.
No.
Nr. dis-
played
Display
Description Range
Default
setting
UM
Access
type
Category
M1 48
DHW
tank
set-
point
Establishes the DHW indirect storage tank set-point
Par. 35 in mode 2.
104-160
(40-71)
122 (50) °F (°C) U DHW
M1 92
Fan
Speed
Maxi-
mum
Denes the fan rpm at max. power (it depends on
the model and is dened at Par. 98).
0-12750
Dened
by Par. 98
RPM I General
M1 93
Fan
Speed
Mini-
mum
Denes the fan rpm at minimum power (it depends
on the model and is dened at Par. 98).
0-12750
Dened
by Par. 98
RPM I General
M1 94
Fan
Speed
Ignition
Denes the fan rpm when the boiler is switched on
(it depends on the model and is dened at Par. 98).
0-12750
Dened
by Par. 98
RPM I General
M1 116
Prog.
Input 1.
The value of this parameter is dened by Par. 97.
0 Disabled
1 Water pressure
sensor
2 CH ow switch
3 Flue pressure
switch
Dened
by Par. 97
I General
M1 117
Prog
Input 2.
The value of this parameter is dened by Par. 97.
0 Disabled
1 DHW ow
sensor
2 DHW ow
switch
3 CH ow sensor
Dened
by Par. 97
I General
M1 118
Prog
Input 3.
The value of this parameter is dened by Par. 97.
0 Disabled
1 Drain switch
2 Gas pressure
switch
Dened
by Par. 97
I General
M1 120
Prog
Input 5.
The value of this parameter is dened by Par. 97.
0 Disabled
1 T_Return
sensor
2 Extern switch
Dened
by Par. 97
I General
M1 121
Prog
Input 6.
The value of this parameter is dened by Par. 97.
0 Disabled
1 T_Flue sensor
2 Flue switch
3 APS switch
Dened
by Par. 97
I General
M1 122
Prog
Input 7.
The value of this parameter is dened by Par. 97.
0 Disabled
1 T_Flue_2
sensor
2 T_Flue_2 + Bl.
Flue
3 T_System
sensor
4 Blocked Flue
switch
5 Cascade
Sensor
Dened
by Par. 97
I General
M1 123
Prog
Input 8.
The value of this parameter is dened by Par. 97.
0 Disabled
1 T_Flue_2
sensor
2 T_Flue_2 + Bl.
Flue
3 T_System
Sensor
4 Blocked Flue
Switch
5 Cascade
Sensor
Dened
by Par. 97
I General

Table of Contents