5.18 List of parameters
Parameter
Number of
elements
Unit of
measure-
ment
Modification
Values interval
Degree of
precision
Predefined
setting
Access mode
No.
par.
Description Min. Max.
100 General parameters
102 Control box identification date 1 - Reading only 0 255 1 Info mode
103 Control box identification number 1 - Reading only 0 65535 1 Info mode
104 Identification number of the group of parameters set 1 - Reading only 0 255 1 Info mode
105 Version of the group of parameters set 1 - Reading only 0 0xFFFF 1 Info mode
107 Software version 1 - Reading only 0 0xFFFF 1 Info mode
113 Burner identification 1 - Modification 0 99999999 1 Not defined Info mode
121
Manual setting of output
Not defined = automatic operation
1-
Modification /
zero setting
0% 100% 0.1% Not defined Service mode
125
Frequency of main power supply
0 = 50 Hz
1 = 60 Hz
1 - Modification 0 1 1 0 Parameters mode
126 Brightness of display 1 - Modification 0% 100% 1% 75% Parameters mode
128
Fuel meter: Led pulse valence
(led pulses / volumetric flow units)
1 - Modification 0 400 0,01 0 Parameters mode
130
Eliminate visualisation error chronology
To eliminate the visualisation, set the parameter to 1, then to 2
Answer 0: Process successful
Answer -1: Time-out of 1_2 - Sequence
1 - Modification -5 2 1 0 Parameters mode
141
Remote management of control box
0 = off
1 = Modbus
2 = reserved
- Modification 0 2 1 0 Parameters mode
142
Standby time before a new attempt in event of fault
in communication
s Modification 0 s 7200 s 1s 600 s Parameters mode
143 Reserved - Modification 1 8 1 1 Info mode
144 Reserved - Modification 10s 60s 1s 30 s Parameters mode
145 Peripheral address for Modbus - Modification 1 247 1 1 Parameters mode
146
Baud Rate for Modbus
0 = 9600
1 = 19200
- Modification 0 1 1 0 Parameters mode
147
Parity for Modbus
0 = none
1 = odd
2 = even
1 - Modification 0 2 1 0 Parameters mode
Start-up, calibration and operation of the burner
5