Technical description of the burner
4.8 Firing rates
The RS 70 - 100 - 130 burners can operate in two modes: one-
stage or two-stage.
The MAXIMUM OUTPUT is selected from within area A (and B
for RS 130)(Fig. 2). To use also area B (RS 130) the combustion
head needs to be re-calibrated. See “Combustion head pre-cali-
bration” on page 17.
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
RS 70 = 192 kW
RS 100 = 232 kW
RS 130 = 372 KW
WARNING
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1,013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
shown on page 18.
Pressure in
combustion chamber - mbar
Thermal power - kW
Fig. 2
RS 70
D950
Pressure in
combustion chamber - mbar
Thermal power - kW
RS 100
Pressure in
combustion chamber - mbar
Thermal power - kW
RS 130