Installation and Programming Manual
3-54
DIALER: CONTROLS
Quick Key Item Default Explanation
5 5 CONTROLS --- controls aspects of the Pro-24’s dialer operation
5 5 01 MS Enable YES if YES:
enables communication with the Central Station to
report alarm, trouble, and supervisory events
if NO:
no communication with the Central Station is possible;
choose NO for installations which are NOT monitored
by a Central Station
5 5 02 FM Enable YES if YES:
enables “Follow Me” communication (see below)
if NO:
disables “Follow Me” communication
Follow Me
In addition to Central Station reporting, the Pro-24 employs a Follow-Me feature, in which
a standard phone call–reporting a system event–can be made to a designated phone number.
This procedure is generally useful for informing a homeowner at work, or a business owner at
home, that there has been an alarm at a specific premises. There are two variations of the
Follow-Me operation:
using a standard phone call
:
in the first, the Follow-Me call conveys a series of tones representing the active alarm
(e.g. burglary or fire) and can be employed in a partition-by-partition basis
the selected phone number(s) being called are programmed by accessing the User
Functions Mode (see User Functions in the Pro-24 User’s Manual)
using a phone call to a pager
:
the Follow-Me call can go to a pager, which, if numeric or alphanumeric, can display
specific event (e.g. alarm, arm/disarm) and partition information
5 5 03 U/D Enable YES if YES:
permits remote communication between the Alarm
Company and the Pro-24 through the
Upload/Download Software
doing so permits the modification of an installation’s
configuration, obtaining status information, and
issuing panel commands–all through remote means
if NO:
disables remote communication as described above
5 5 04 Call Delay YES if YES:
event reports to the Central Station are delayed for
15 seconds after they’re detected
if NO:
event reports are sent immediately
5 5 05 Dial Tone YES if YES:
wait a short, selectable, interval (see page 3-57) to
detect dial tone before dialing the Central Station
if NO:
dial without waiting
INSTALLER PROG:
5)DAILER