Input range table
Thermocouple input
Code
Input type
Input Range
0 to 200
°
CK01
K
0 to 400
°
CK02
0 to 600
°
CK03
0 to 800
°
CK04
0 to 1000
°
CK05
0 to 1200
°
CK06
0 to 1372
°
CK07
0 to 100
°
CK13
0 to 300
°
CK14
0 to 450
°
CK17
0 to 500
°
CK20
0 to 800
°
FKA1
0 to 1600
°
FKA2
0 to 2502
°
FKA3
20 to 70
°
FKA9
0 to 200
°
CJ01
J
0 to 400
°
CJ02
0 to 600
°
CJ03
0 to 800
°
CJ04
0 to 1000
°
CJ05
0 to 1200
°
CJ06
0 to 450
°
CJ10
0 to 800
°
FJA1
0 to 1600
°
FJA2
0 to 2192
°
FJA3
0 to 400
°
FJA6
0 to 300
°
FJA7
0 to 1600
°
C
*
1
R01
R
0 to 1769
°
C
*
1
R02
0 to 1350
°
C
*
1
R04
0 to 3200
°
F
*
1
RA1
0 to 3216
°
F
*
1
RA2
0 to 1600
°
C
*
1
S01
S
0 to 1769
°
C
*
1
S02
0 to 3200
°
F
*
1
SA1
0 to 3216
°
F
*
1
SA2
400 to 1800
°
CB01
B
0 to 1820
°
C
*
1
B02
800 to 3200
°
FBA1
0 to 3308
°
F
*
1
BA2
0 to 800
°
CE01
E
0 to 1000
°
CE02
0 to 1600
°
FEA1
0 to 1832
°
FEA2
0 to 1200
°
CN01
N
0 to 1300
°
CN02
0 to 2300
°
FNA1
0 to 2372
°
FNA2
-199.9 to +400.0
°
C
*
2
T01
T
-199.9 to +100.0
°
C
*
2
T02
-100.0 to +200.0
°
CT 03
0.0 to 350.0
°
CT04
-199.9 to +752.0
°
F
*
2
TA1
-100.0 to +200.0
°
F
*
2
TA2
-100.0 to +400.0
°
F
*
2
TA3
0.0 to 450.0
°
FTA4
0.0 to 752.0
°
FTA5
W5Re/
0 to 2000
°
CW01
W26Re
0 to 2320
°
CW02
0 to 4000
°
FWA1
Code
Input type
Input Range
0 to 1300
°
CA01
PL II
0 to 1390
°
CA02
0 to 1200
°
CA03
0 to 2400
°
FAA1
0 to 2534
°
FAA2
-199.9 to +600.0
°
C*
2
U01
U
-199.9 to +100.0
°
C*
2
U02
0.0 to 400.0
°
CU03
-199.9 to +999.9
°
F*
2
UA1
-100.0 to +200.0
°
F*
2
UA2
0.0 to 999.9
°
FUA3
0 to 400
°
CL01
L
0 to 800
°
CL02
0 to 800
°
FLA1
0 to 1600
°
FLA2
RTD input
Code
Input type
Input Range
-199.9 to +649.0
°
CD 01
Pt100
-199.9 to +200.0
°
CD 02
-100.0 to +50.0
°
CD03
-100.0 to +100.0
°
CD 04
-100.0 to +200.0
°
CD 05
0.0 to 50.0
°
CD06
0.0 to 100.0
°
CD07
0.0 to 200.0
°
CD08
0.0 to 300.0
°
CD09
0.0 to 500.0
°
CD10
-199.9 to +999.9
°
FD A1
-199.9 to +400.0
°
FD A2
-199.9 to +200.0
°
FD A3
-100.0 to +100.0
°
FD A4
-100.0 to +300.0
°
FD A5
0.0 to 100.0
°
FDA6
0.0 to 200.0
°
FDA7
0.0 to 400.0
°
FDA8
0.0 to 500.0
°
FDA9
-199.9 to +649.0
°
CP 01
JPt100
-199.9 to +200.0
°
CP 02
-100.0 to +50.0
°
CP03
-100.0 to +100.0
°
CP 04
-100.0 to +200.0
°
CP 05
0.0 to 50.0
°
CP06
0.0 to 100.0
°
CP07
0.0 to 200.0
°
CP08
0.0 to 300.0
°
CP09
0.0 to 500.0
°
CP10
Voltage input and Current input
Code
Input type
Input Range
0 to 5 V DC 4 01
0 to 10 V DC
*
501
1 to 5 V DC 0.0 to
100.0 %
601
0 to 20 mA DC 7 01
4 to 20 mA DC 8 01
*
Z-1010 specification
*1: 0 to 399 °C/0 to 751 °F: Accuracy is not guaranteed.
*2: -199.9 to -100.0 °C/-199.9 to -148.0 °F : Accuracy is not guaranteed.