3. SETTING FOR COMMUNICATION
IMCB03-E4
11
3.5 Data bit configuration setting
Set the data bit configuration during communication by using numerals from 0 to 5. Press the UP or
DOWN key to change the numeral.
Symbol Name Setting range Description
Factory set
value
Data bit
configuration
0 to 5
See *A
Selects data bit configuration
during communication.
0
bIT
*A
Setting Data bit [bit] Parity bit Stop bit [bit]
0 8 None 1
1 8 None 2
27 Even 1
37 Even 2
47 Odd 1
57 Odd 2
Set the same data bit configuration to both the controller and connecting host computer.
When the communication parameter was changed, always turn on the power again.
Otherwise, no communication is performed by using the changed value.
If key operation is not performed for more than 1 minute without pressing the SET key
after the data bit configuration is set, the controller is automatically changed to PV/SV
display mode. In this case, the set data bit configuration returns to the value before the
setting is changed.