1. Press MENU.
2. Press and hold TECH SET for 3 seconds.
3. Congure the installer options as desired using the table below.
4. Use and to change settings and the NEW STEP or PREV STEP to
move from one option to another.
Note: Only press DONE when you want to exit the Installer Setup Options.
Feature
Filter Change
Reminder
Room
Temperature
Calibration
Minimum
Compressor On
Time
Compressor
Short Cycle
Delay
Cooling
Differential
Heating
Differential
Adjustment
Options
The lter change
reminder can
be adjusted
from OFF to
2000 hours
in 50 hour
increments.
The room
temperature
display can
be adjusted
to read 3°
above or below
the factory
calibrated
temperature.
The minimum
compressor
run time can be
adjusted from
OFF to 3, 4, or 5
minutes. If 3, 4,
or 5 is selected,
the compressor
will run for at least
the selected time
before turning off
(although the fan
may continue to
run for a short time).
The
compressor
short cycle
delay setting
can be
removed by
selecting OFF.
The cooling
differential
setting is
adjustable from
0.2°F to 2°F
The heating
differential
setting is
adjustable from
0.2°F to 2°F.
INSTALLER SETUP MENU
8

Other manuals for Robertshaw RS8210

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Robertshaw RS8210 and is the answer not in the manual?

Robertshaw RS8210 Specifications

General IconGeneral
BrandRobertshaw
ModelRS8210
CategoryThermostat
LanguageEnglish

Related product manuals