Rockwell Automation Publication 1769-IN088A-EN-P - February 2011 155
I/O Memory Mapping Chapter 3
The bits are defined as follows:
E = Channel Enable: (0 = Disabled, 1 = output 0 and hold Enabled,
process changes)
Reserved = Set to zero
SIU = System interrupt low clamp, under-range alarms: (0 = Disabled, 1 =
Enabled)
SIO = System interrupt high clamp, over-range alarms: (0 = Disabled, 1 =
Enabled)
LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled, 1 =
Enabled)
ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by
fault states.)
FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)
PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)
HI = Hold for initialization: (0 = Disabled, 1 = Enabled)
PFE = Program/idle to fault enable: (0 = Disabled, 1 Enabled)
Channel Configuration Words
The first two words of each eight word group in the configuration file allow you
to change the parameters of each channel independently. For example, words 8
and 9 correspond to channel 1 while words 56 and 57 correspond to channel 7.
Define Indicate this These bit settings
1514131211109876543210
Program
(Idle) to
Fault Enable
Program (Idle)
Mode Data
Applied
(1)
00000000 0
Fault Mode Data
Applied
(1)
00000000 1
Hold for
Initialization
Disabled
0 0 0 0 0 0 0 0 0
Enabled 00000000 1
Program
(Idle) Mode
Hold Last State
(1)
0 0 0 0 0 0 0 0 0
User-Defined
Value
(1)
00000000 1
Fault Mode Hold Last State
(1)
0 0 0 0 0 0 0 0 0
User-Defined
Fault Value
(1)
00000000 1
Enable
Ramping
Disabled 0 0 0 0 0 0 0 0 0
Enabled 00000000 1
System
Interrupt
High Clamp
Disabled 0 0 0 0 0 0 0 0 0
Enabled 0 0 0 0 0 0 0 0 1