22 Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 2        Module Wiring
1769-IF4
Compact voltage/current analog input module
+
–
V in 0 +
V/I in 0 -
I in 0+
ANLG Com
V in 1 +
V/I in 1 -
I in 1+
ANLG Com
V in 2 +
V/I in 2 -
I in 2+
ANLG Com
V in 3 +
V/I in 3 -
I in 3+
ANLG Com
DC NEUT
+24V DC
+
-
1769-IF4 Differen tial Inputs
+
V in 0 +
V/I in 0 -
I in 0 +
ANLG Com
V in 1 +
V/I in 1 -
I in 1 +
ANLG Com
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
+24V DC
DC NEUT
+
+
+
-
+
-
1769-IF4 Single-ended Sensor/Transmitter  Inputs
1769-IF4 Mixed Transmitter Inputs
+
V in 0 +
V/I in 0 -
I in 0 +
ANLG Com
V in 1 +
V/I in 1 -
I in 1 +
ANLG Com
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
+24V DC
DC NEUT
+
+
+
+
+
+
–
–
–
–
–
–
+
–
The external power supply must be rated Class 2, with a 24V DC 
range of 20.4…26.4V DC and 60 mA minimum. Series B and 
later modules support this option.
External 24V 
DC Power 
Supply
External 24V 
DC Power 
Supply
External 24V 
DC Power 
Supply
Analog Source
Belden 8761 Cable (or equivalent)
Earth ground the shield 
locally at the module.
Sensor/
Transmitter 
Supply
Current
Voltage
Voltage
Sensor/
Transmitter 
Supply
Single-ended 
Voltage
Differential 
Voltage
Differential 
Current
Two-wire 
Current
Signal
Signal
Ground
Signal
Ground
Signal
Signal
Signal
Signal