26 Publication 1769-UM020A-EN-P - December 2009
Chapter 2 Installation and Wiring
3. Strip about 5 mm (3/16 in.) of insulation away to expose the end
of the wire.
4. At one end of the cable, twist the drain wire and foil shield
together.
Under normal conditions, this drain wire and shield junction
must be connected to earth ground, via a panel or DIN rail
mounting screw at the analog I/O module end. Keep the length
of the drain wire as short as possible.
In environments where high frequency noise may be present, it
may be necessary to also ground the cable shields to earth via a
0.1 µF capacitor at the sensor end.
5. At the other end of the cable, cut the drain wire and foil shield
back to the cable, unless the sensor end of the cable requires
the shields to be connected to earth ground via the capacitor
described in step 4
.
6. Connect the signal wires to the terminal block.
7. Connect the other end of the cable to the analog output device.
8. Repeat steps 1
6 for each channel on the module.
Terminal Layout
ATTENTION
Be careful when stripping wires. Wire fragments that
fall into a module could cause damage when you cycle
power.
ANLG Com
ANLG Com
I out 2+
I out 3+
I out 1+
I out 0+
V out 2+
V out 3+
V out 1+
V out 0+

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley 1769-OF4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley 1769-OF4 and is the answer not in the manual?

Rockwell Automation Allen-Bradley 1769-OF4 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley 1769-OF4
CategoryControl Unit
LanguageEnglish

Related product manuals