28 Rockwell Automation Publication 1756-UM004C-EN-P - June 2021
Chapter 2 Connect to the EtherNet/IP Network
Redundant Adapter
Considerations Setting the
IP Address
The following are considerations when using two 1756-EN4TR modules as a
Redundant Adapter Pair.
Default Class C addresses like 192.168.1.x can be set using rotary switches
on the module in any mode. This includes the mode switch set at 7 or 9.
IP address assignments other than default Class C can only be set in
normal mode, where the switch is set to 9.
Both 1756-EN4TR modules must be set to the same IP address before
switching to Redundant Adapter Mode, where the switch is set to 7.
You must reserve an IP+1 address that is taken automatically by the
secondary.
For example, if the primary address is 192.168.1.1, the address
192.168.1.2 must be reserved.
To set the IP address for redundant adapters use the following steps.
1. Insert one module into chassis in the standard mode (rotary switch set to 9).
2. Set the IP address on the module.
3. Remove the module from the chassis.
4. Insert a second module into the chassis.
5. Set the same IP address on the second module as you set on the first
module.
6. Put both modules in redundant adapter mode, and put the modules in
slots 0 and 1.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley ControlLogix 1756-EN2F and is the answer not in the manual?

Rockwell Automation Allen-Bradley ControlLogix 1756-EN2F Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley ControlLogix 1756-EN2F
CategoryNetwork Hardware
LanguageEnglish

Related product manuals