22 Rockwell Automation Publication 750-RM100A-EN-P - August 2019
Chapter 2 AC Line Tuning
Figure 10 - Voltage Regulator and Gains Block Diagram
Current Regulator Gains—Manual Adjustment
PowerFlex 755T products allow individual manual adjustment of the
proportional and integral terms that are used by the current regulator. To enable
manual adjustment of the proportional and integral terms, set 13:74 [Cur Reg C/
U Sel] to 1 ‘User Entered’. This setting switches the gains that are used by the
current regulator from the calculated values to values that are entered in
parameters 13:77 [u Cur Reg Kp] and 13:79 [u Cur Reg Ki].
It is recommended to begin manual adjustment with the suggested gain start
points. To initiate the transfer of these values, toggle 13:74 [Cur Reg C/U Sel] to
2 ‘LoadCalcData’. When this option is selected, the calculated gains values are
copied to the user entered gain parameters. When the transfer is complete, 13:54
[Volt Reg C/U Sel] will automatically set to 1 ‘User Entered’ for manual
adjustment.
Auto Gain
Calculation
PI Regulator
55
56
Volt Reg BW
Volt Reg Damping
0
1
54
Volt Reg C/U Sel
0
1
59
u Volt Reg Ki
57
u Volt Reg Kp
c Volt Reg Ki 60
c Volt Reg Kp
58
DC Bus Command
50
VoltRefGen [G3]
Internal Bus Capacitance
Metering [D5]
DC Bus Obs
A[2]
52
Ext Bus Cap
VbusErr
VbusRegKi
VbusRegKp
IqRefVbusReg
Volt Reg C/U Sel Selector:
0- Calculated
1- User Entered
Total Sys Cap
DcBusObs [C1]
BusRegIntegTerm
BusRegPropTerm
BusObsMode
BusObsMode (320):
0- BusObs Only
1- BusObsVltEst
320
3
Port 0,DC Bus Volts
0
1
DC Bus Obs
[H5]
BusObs Volt Est
1
0,2
BusDistRejMode(300):
0- Disabled
1-BusObserver.
2- FF Power.
300
BusCompMode
Parameter No. Parameter Name Definition
13:54 Volt Reg C/U Sel 0 = Calculated, 1 = User Entered, 2 = Load Calculated Data
13:55 Volt Reg BW Voltage regulator bandwidth in Hz
13:56 Volt Reg Damping Voltage regulator damping factor
13:57 u Volt Reg Kp User entered voltage regulator proportional gain
13:58 c Volt Reg Kp Calculated voltage regulator proportional gain
13:59 u Volt Reg Ki User entered voltage regulator integral gain
13:60 c Volt Reg Ki Calculated voltage regulator integral gain

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 700 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 700 Series and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 700 Series Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 700 Series
CategoryDC Drives
LanguageEnglish

Related product manuals