Programming and Parameters 3-31
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Advanced Program Group (continued)
A100 [Fault Clear]
Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network
communications.
Options 0 “Ready/Idle” (Default)
1 “Reset Fault”
2 “Clear Buffer” (Parameters d007
-d009 [Fault x Code])
A101 [Program Lock]
Protects parameters against change by unauthorized personnel.
Options 0 “Unlocked” (Default)
1 “Locked”
A102 [Testpoint Sel] Related Parameter(s): d019
Used by Rockwell Automation field service personnel.
Values Default: 400
Min/Max: 0/FFFF
Display: 1 Hex
A103 [Comm Data Rate] Related Parameter(s): d015
Sets the serial port rate for the RS485 (DSI) port.
Important: Power to drive must be cycled before any changes will affect drive operation.
Options 0 “1200”
1 “2400”
2 “4800”
3 “9600” (Default)
4 “19.2K”
5 “38.4K”
A104 [Comm Node Addr] Related Parameter(s): d015
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Important: Power to drive must be cycled before any changes will affect drive operation.
Values Default: 100
Min/Max: 1/247
Display: 1
22B-UM001.book Page 31 Tuesday, May 30, 2017 5:22 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen Bradley PowerFlex40 and is the answer not in the manual?

Rockwell Automation Allen Bradley PowerFlex40 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen Bradley PowerFlex40
CategoryDC Drives
LanguageEnglish

Related product manuals