Programming and Parameters 3-35
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Advanced Program Group (continued)
A119 [Skip Frequency] Related Parameter(s): A120
Sets the frequency at which the drive will not operate.
A setting of 0 disables this parameter.
Values Default: 0 Hz
Min/Max: 0/400 Hz
Display: 1 Hz
A120 [Skip Freq Band] Related Parameter(s): A119
Determines the bandwidth around A119 [Skip Frequency]. A120 [Skip Frequency Band] is split
applying 1/2 above and 1/2 below the actual skip frequency.
A setting of 0.0 disables this parameter.
Values Default: 0.0 Hz
Min/Max: 0.0/30.0 Hz
Display: 0.1 Hz
Frequency
Time
Skip Frequency
Command
Frequency
Drive Output
Frequency
2x Skip
Frequency Band
A121 [Stall Fault Time]
Sets the time that the drive will remain in stall mode before a fault is issued.
Options 0 “60 Seconds” (Default)
1 “120 Seconds
2 “240 Seconds
3 “360 Seconds
4 “480 Seconds
5 “Flt Disabled”
22B-UM001.book Page 35 Tuesday, May 30, 2017 5:22 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen Bradley PowerFlex40 and is the answer not in the manual?

Rockwell Automation Allen Bradley PowerFlex40 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen Bradley PowerFlex40
CategoryDC Drives
LanguageEnglish

Related product manuals