The MSR300 safety relay example shows the input wiring where no
simultaneity is required.
Connected Components
Workbench Example -
Muting with E-stop
Muting is accomplished with one safety monitor function. The muting
function turns on the output with automatic reset and feedback monitoring.
The E-stop turns OFF the outputs and requires a monitored manual reset. The
E-stop turns OFF the outputs with the Output Loop block, which takes the E-
stop output and logically ANDs it with the light curtain output.
Response Time MSR310P = 26 ms + 6 ms per connected input
DIS = Inputs: 25 ms, Mat operation: 30 ms, SWS Fault: 45 ms
DI = Inputs: 35 ms, Mat operation: 40 ms, SWS Fault: 45 ms
EM = 35 ms, SWS output = 25 ms
EMD = 35 ms plus the timer selection, SWS output = 25 ms