Maintenance
Repair
126 MagneMotion
Rockwell Automation Publication MMI-UM037A-EN-P - April 2020
Replace Bushings on Pallet
The bushings used to locate the pallet can be removed and replaced if they become damaged
or worn due to extended use.
Required Tools and Equipment
100-0097-30 – Loctite 243, Thread locker Anaerobic Adhesive, Blue.
200-2342-00 – Tapered Bushing, Hole, Pallet, ML-PL.
200-2342-01 – Tapered Bushing, SLOT, Pallet, ML-PL.
100-2457-01 – Pin, Dowel, Ø2 mm X 5 mm L, 18-8 SS, per DIN 7-M6 (2X).
100-2202-05 – Nut, Jam, Hex, M6x1, 18-8 (A2) SS, per DIN 439B (2X).
Isopropyl Alcohol.
Torque wrench with the following bits:
•6mm.
CAUTION
Strong Magnets
To avoid severe injury, people with pacemakers and other
medical electronic implants must stay away from the magnet
array on the vehicles (pucks).
To avoid injury from strong magnetic attractive forces:
Handle only one vehicle (puck) or magnet array at a time.
Do not place any body parts, such as fingers, between a
vehicle (puck) or magnet array and any ferrous material
or another magnet array.
Vehicles (pucks) or magnet arrays not being used must be
secured individually in isolated packaging.
To avoid damage to watches, instruments, electronics, and
magnetic media, keep metal tools, metal objects, magnetic
media (for example, memory disks/chips, credit cards, and
tapes) and electronics away from the magnet arrays.