LCD METER ASSEMBLY
Figure 1 shows the mounting hardware required to properly
install the LCD meter on a transmitter or in the field signal
indicator. This mounting hardware may also be used with the
Rosemount universal (analog) meter.
LCD METER CONFIGURATION
The LCD meter may be configured to meet specific
requirements by using the left and right configuration buttons
located on the meter face as shown on the cover. The analog bar
graph is also shown on the cover. The 20-segment bar graph is
factory calibrated and represents 4–20 mA directly.
No calibration equipment is required to configure the LCD
meter, but between 4 and 20 mA must be flowing through the
loop. The actual value of the current is not significant. In addition,
meter configuration does not affect the transmitter/loop current.
Use the following meter configuration procedure to properly
configure the LCD meter.
NOTE
The LCD meter time-out is approximately 16 seconds. If keys are
not pressed within this period, the indicator reverts to reading the
current signal.