Controller Functionality
AYC-Fx4 and AYC-Gx4 family manual Page 43
auxiliary relay shunts the door sensor for the duration of the shunt
time, as defined by the auxiliary setting. If the door is left open
longer than the shunt time, an alarm will be triggered.
Auxiliary Mode 5
Auxiliary input function: Door Monitor
Auxiliary output activated by: Shunt (explanation below)
E.g. In auxiliary mode 5, the controller is capable of shunting an
alarm system. In this mode, the auxiliary input is to be wired to the
magnetic contact switch on the door. The auxiliary relay is wired
to the alarm system. Without a valid code entered, the auxiliary
relay will match the condition of the magnetic contact switch; if
the door opens, the auxiliary relay will open; if the door closes, the
auxiliary relay will close. When a valid code is entered, a count
down for maximum shunt time, as defined by the auxiliary setting,
begins; if the door is not closed before the maximum shunt time,
the alarm will be triggered.
Auxiliary Mode 6
Auxiliary input function: Door Monitor
Auxiliary output activated by: Forced entry
E.g. In auxiliary mode 6, the controller can trigger the auxiliary
relay if the door has been forced. If the Siren Settings is enabled
the siren will be activated.
In this mode, the auxiliary input functions as a door monitor switch
and is wired to the magnetic contact switch on the door. The
auxiliary relay is to be wired to the alarm system. If the door is
forced open, the controller will wait for the period of the forced
door delay time to elapse and then, it will activate the auxiliary
relay. The auxiliary setting sets the forced door delay period.