 Troubleshooting 29 
6.6 EH 0E(Water-Level Alarm Malfunction Diagnosis and Solution)
Description: If the sampling voltage is not 5V, the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Water-level switch
• Water pump
• Indoor PCB
Shut off the power supply and
turn it on 2 minutes later.
Shut off the power supply and
turn it on 2 minutes later.
Does a problem
remain?
Does a problem
remain?
YES
Is the water-level switch
inserted properly?
Is the water-level switch
inserted properly?
Replace the indoor main PCB.
Replace the indoor main PCB.
YES
The unit is operating normally.
The unit is operating normally.
NO
Insert the water-level
switch properly
Insert the water-level
switch properly
NO
Is the water-level switch
broken?
Is the water-level switch
broken?
Replace the water-level switch
Replace the water-level switchNO
YES
Replace the water pump
Replace the water pump
Does a problem
remain?
Does a problem
remain?
YES
The unit is operating normally.NO

Table of Contents

Other manuals for Rotenso LCAC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotenso LCAC Series and is the answer not in the manual?

Rotenso LCAC Series Specifications

General IconGeneral
BrandRotenso
ModelLCAC Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals