MODEL: N74A1-63510/N74A3-63610/N74B1-63510B/N74B3-63610B
14
Regenerat
ion Time
02:00
02:00
00:00
23:59
Regeneration time” light on
Resin
Volume
20L
20L
5500L
Resin volume in brine tank (L)
Feed
Water
Hardness
Yd1.2
1.2
0.19.9
Feed water hardness (mmol/L)
Exchange
Factor
AL.65
0.65
0.300.99
Relate to the raw water
hardness. When hardness is
higher, the factor is smaller.
Water
Treatment
Capacity
10m
3
099.99 m
3
Water treatment capacity in one
circle (m
3
)
Backwash
Time
10min.
09959
Backwash time(Minute)
Brine &
Slow
Rinse
Time
60min.
09959
Brine &Slow rinse time(Minute)
Brine Refill
Time
5min.
09959
Brine refill time(Minute)
Fast Rinse
Time
10min.
09959
Fast rinse time(Minute)
Maximum
Interval
Regenerat
ion Days
H-30
30
040
Regenerate on the day even
through the available volume of
treated water does not drop to
zero (0).
Output
Control
Mode
b-01
01
01 or 02
Signal turn on start of
regeneration and shut off end of
regeneration. (refer to P4)
Signal available only intervals of
regeneration cycles and in
service. (refer to P4)

Table of Contents