Operating manual - ChillPAC and LP ChillPAC Mk 3
60/68
010823 en 2021.06
Appendices
Check the settings
You can check your settings
by pressing twice.
Press
to return to
default screen.
AKS 4100
COAX D22
280 mm
(0%) 4
mA
210
mm
(100
%) 20 mA
060 mm
After running the quick set-up, go to the supervisor menu and change the following parameters:
2.3.2 Blocking distance
2.3.3 Time constant
2.5.3 Epsilon R gas constant (Er gas)
Change to the value indicated for the temperature of the media. If a media range is given,
choose the value of the lowest operating media temperature. See the List of Er gas constant in
Fig. 39.
2.5.7 Level threshold
4.1.1 Full area
4.1.2 Empty area.
The supervisor menu is protected by a passcode.
1. Name the buttons on the AKS head 1-2-3-4 from left to right, see Fig. 29.
Fig. 29
Supervisor passcode = 1-2-3-4-1-2
2. Press Arrow right (no. 1) once - the first digit 1 is marked, see Fig. 30.
Fig. 30
1
23
4