Conguration
TEST ALARM &
BATTERY ALARM
CODE
DATA COMMENTS
LMS phone number *16* - - - - - - - - - # LMS (Lift Monitoring System) phone number
to alarm receiver or SLCC.
Test alarm *17* - - - - - - - - - # Phone number to send testalarm to alarm
receiver or SLCC.
Call back test alarm *19* - - - - - - - - - # Triggers a test alarm event to a user selected
phone number.
The call is made af ter the conguration is
terminated.
Days between tests *27* - - # Number of days between test alarms, 00-99
days.
Always two digits.
Max 3 days according to EN 81-28.
00 = No test alarms
Test alarm protocol *31* - # 0 = P100
3 = CPC
4 = Caller ID
ALARM TYPE
CODE
DATA COMMENTS
Alarm type 1st number *41* - - #
Only when using CPC as alarm protocol
Normally 10 or 27, check with your alarm
company!
Alarm type 2nd number *42* - - #
Alarm type 3rd number *43* - - #
Alarm type 4th number *44* - - #
Alarm type LMS *45* - - # LMS (Lift Monitoring System)
(Battery alarm)
Normally 17
Alarm type Test alarm *46* - - # Normally 26