56
A5 Control Optimization Parameters
Function
Code
Parameter
Name
Setting Range Default Property
A5-00
DPWM switchover
frequency upper limit
5.00Hz ~ maximum
frequency
8.00Hz ☆
A5-01 PWM modulation mode
0: Asynchronous
modulation
1: Synchronous
modulation
0 ☆
A5-02
Dead zone
compensation mode
selection
0: No compensation
1: Compensation mode 1
1 ☆
A5-03 Random PWM depth
0: Random PWM invalid
1 ~ 10: PWM carrier
frequency random depth
0 ☆
A5-04 Rapid current limit
0: Disabled
1: Enabled
1 ☆
A5-05
Current detection
compensation
0 ~ 100 5 ☆
A5-06 Undervoltage threshold 210 ~ 420V 350V ☆
A5-07
SVC optimization mode
selection
1: Optimization mode 1
2: Optimization mode 2
1 ☆
A5-08
Dead-zone time
adjustment
100% ~ 200% 150% ★
A5-09 Overvoltage threshold 200.0V ~ 2500.0V
Model
dependant
★
6.1 Brief introduction of function code