EasyManua.ls Logo

Samson 3730-2 - Set Point Deviation Histogram

Samson 3730-2
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40 EB 8389 EN
Statistical information
4.4 Set point deviation histo-
gram
3730-2 3730-3 3731-3 3730-4 3730-5 3731-5
The set point deviation histogram contains a
statistical analysis of any set point deviations
recorded. It provides information on to which
extent a set point deviation has occurred
during the valve service life and whether
faults may occur due to a restricted working
range or due to seat leakage.
Data are recorded in the background re-
gardless of the operating mode selected. Da-
ta logging does not need to be activated.
The positioner records the set point deviation
every second and assigns the data into pre-
dened classes. The distribution showing
how often the set point deviation remained
within a class is shown in a bar graph.
The 'Average value e long' indicates the
average class assignment of the set point
deviation over the 'Observation period.'
The 'Number of measurement values'
shows the total number of values were
recorded during the 'Observation peri-
od'.
'Observation period'
'Absolute value of max. set point devia-
tion' (not Type3730-4): The largest set
point deviation measured during the ob-
servation period
'Min. set point deviation' (Type3730-4
only): The smallest set point deviation
measured over the observation period.
'Max. set point deviation' (Type3730-4
only): The largest set point deviation
measured over the observation period.
The measured data are saved in a non-vola-
tile memory in the positioner every 24 hours.
Fig.4: Diagnosis > Statistical information > Set point deviation histogram e