SH 8384-3 EN 7
Technical data (excerpt from EB8384-3)
Type 3730-3 Positioner: also observe the technical data in the test certicates for explosion-protected versions
Sensitivity ≤0.1%
Transit time Venting or lling with air adjustable separately up to 240s by software.
Air output
capacity
To ll actuator
with air
At Δp = 6 bar: 8.5 m
n
³/h · At Δp = 1.4 bar: 3.0 m
n
³/h · K
Vmax (20 °C)
= 0.09
To vent actuator At Δp = 6 bar: 14.0 m
n
³/h · At Δp = 1.4 bar: 4.5 m
n
³/h · K
Vmax (20 °C)
= 0.15
Permissible ambient tem-
perature
–20 to +80°C (all versions)
–45 to +80°C with metal cable gland
Observe the limits in the test certicate for explosion-protected versions.
Use in safety-instrumented
systems (SIL)
Observing the requirements of IEC61508, the systematic capability of the pilot valve
for emergency venting as a component in safety-instrumented systems is given.
Use is possible on observing the requirements of IEC61511 and the required hard-
ware fault tolerance in safety-instrumented systems up to SIL2 (single device/HFT=0)
and SIL3 (redundant conguration/HFT=1).
Safety-relevant options
Solenoid valve · Approval according to IEC61508/SIL · Emergency venting function
Input
24VDC · Electrical isolation and reverse polarity protection · Static destruction limit
40V
Current consumption I =
U – 5.7V
3840Ω
(corresponding to 4.8mA at 24V/114mW)
Signal '0' (no response) <12V (emergency shutdown at 0V)
Signal '1' (response) > 19V
Service life >5x10
6
switching cycles
K
V
coefcient 0.15
Use in safety-instrumented
systems acc. to IEC61508/
SIL
Same as positioner pneumatics
Inductive limit contact by Pepperl+Fuchs · Function: safety-related end position monitoring
For connection to switching amplier according to EN60947-5-6.
Can be used in combination with a software limit contact.
SJ2-SN proximity switch Measuring plate not detected: ≥3mA · Measuring plate detected: ≤1mA