EB 6116 EN 17
Design and principle of operation
Dynamic response
Limitingfrequency 5.3Hz
Phase shift –130°
Variable position
Max.3.5%dependingonattachment:±1%inhorizontalposition(Type6109)
Max.1%dependingonattachment:±0.3%inhorizontalposition(Type6112)
Ambient conditions, degree of protection, compliance and weights
Storage temperature –45to+80°C
Ambient temperature
11)
WithType6109 –30to+70°C
6)
;–30to+60°C
1)
WithType6112 –40to+70°C
6) 7)
;–40to+60°C
1) 7)
Degree of protection IP54
4)
,IP65
8)
, NEMA 4
Compliance
·
Explosion protection
ATEX, IECEx, ... RefertoTable1
Materials
Enclosure Die-cast aluminum, chromated and plastic coated
Cable gland (standard)
12)
Blackpolyamide(6to12mmclampingrange,–20to+80°C)
Weight
0.85kg
1)
Details(includingelectricspecicationsandinstallationinstructions)insection10.2(ECtypeexaminationcerti-
cate)
2)
Measured with average output pressure
3)
Measuredwith2mhosewith4mminsidediameter
4)
Observe recommended mounting position.
5)
Seesection3.1whencombinedwithapositioner
6)
Devices without explosion protection
7)
Specialversionsdownto–45°Cavailableonrequest
8)
Possible by using accessories
9)
Themaximumpossibleoutputpressureis8bar.
10)
Initialvalueraisedupto3.0bar(specialversion)
11)
Metalcableglandsandventplugsarerequiredfortemperaturesbelow–20°C.
12)
Devices with type of protection "Flameproof enclosure" are delivered without cable gland.
Dimensions
The dimensions for the i/p converters are included on the next pages.