16 EB 6116 EN
Design and principle of operation
3.2 Technical data
No explosion protection Type6116-0
With explosion protection Types6116-1/-2/-3/-4/-5/-6/-7
Input
5)
4to20mA,othersignalsonrequest
Minimumcurrent>3.6mA,loadimpedance≤6V(correspondingto300Ωat
20mA)
Versionswithexplosionprotection:loadimpedance7V(correspondingto350Ωat
20mA)
Versions without switch-off electronics: R
i
=200Ω±7.5%
Output
5)
0.2to1bar(3to15psi)(Type6109i/pConverterModule)
0.4to2bar(6to30psi)(Type6112i/pConverterModule)
Specialrangesadjustableaccordingtocustomerspecications:
Output range = Initial value
10)
+ Span ∆p with Type6112 i/p Module
0.1to0.4bar + 0.75to1.0bar Module A
0.1to0.4bar + 1.0to1.35bar ModuleB
0.1to0.4bar + 1.35to1.81bar Module C
0.1to0.8bar + 1.81to2.44bar Module D
0.1to0.8bar + 2.44to3.28bar Module E
0.1to0.8bar + 3.28to4.42bar Module F
0.1to1.2bar + 4.42to5.94bar ModuleG
0.1to1.2bar + 5.94to8.0bar ModuleH
9)
Max. air output
capacity
3)
2.0m³/hwithanoutputof0.6bar(0.2to1.0bar)
2.5m³/hwithanoutputof1.2bar(0.4to2.0bar)
8.5m³/hwithanoutputof5.0bar(0.1to8.0bar)
Supply air
Atleast0.4barabovetheuppersignalpressurerangevalue,max.10barwithout
supplypressureregulator,max.6barforExdversion
Air quality acc. to
ISO8573-1:2001
Maximum particle size and density: Class 4 · Oil content: Class 3
Pressuredewpoint:Class3oratleast10Kbelowthelowestambienttemperatureto
be expected
Air consumption
2)
0.08m
n
³/hat1.4bar
0.1m
n
³/hat2.4bar
Max.0.26m
n
³/hat10bar
Characteristic Characteristic: Output linear to input
Hysteresis ≤0.3%ofnalvalue
Deviation from terminal-
based conformity
≤1%ofupperrangevalue(forupperrangevaluesupto5bar);moreexactvalues
on request
≤1.5%ofupperrangevalue(forupperrangevaluesabove5bar)
Effectin%oftheupper
range value
Supplyair:0.1%/0.1bar
2)
Alternatingload,supplyairfailure,interruptionoftheinputcurrent:<0.3%
Ambienttemperature:lowerrangevalue<0.03%/K,span<0.03%/K