EasyManua.ls Logo

Samson 611 - Servicing Explosion-Protected Devices

Samson 611
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38 EB 6116 EN
Maintenance
7.3 Servicing explosion-
protected devices
If a part of the device on which the explosion
protection is based needs to be serviced, the
device must not be put back into operation
untilaqualiedinspectorhasassesseditac-
cording to explosion protection require-
ments,hasissuedaninspectioncerticate,
or given the device a mark of conformity.
Inspectionbyaqualiedinspectorisnotre-
quired if SAMSON performs a routine test
on the device before putting it back into op-
eration. Document the passing of the routine
test by attaching a mark of conformity to the
device.
Replace explosion-protected components on-
ly with original, routine-tested components
by the manufacturer.
Devices that have already been used outside
hazardous areas and are intended for future
use inside hazardous areas must comply
with the safety requirements placed on ser-
viceddevices.Beforebeingoperatedinside
hazardous areas, test the devices according
tothespecicationsforservicingexplo-
sion-protected devices.