EasyManua.ls Logo

Samson Type 3766 - 5 Converting the Positioner

Samson Type 3766
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Converting the positioner
The pneumatic positioner (3766-x...x.04
and higher) can be converted to form a
Type 3767 Electropneumatic Positioner.
Note: Conversion of explosion-protected
versions only on request.
Apart from the Type 6112 i/p Module (see
Table 11), the associated conversion kit in
-
cluding screw gland, fastening screw,
clamps and cables must be ordered.
1. Remove the support with the terminal
case (if existing).
2. Unscrew the connecting plate (3) and re-
move the silicone hose (2). Remove the
guard plate (4) and pneumatic screw
gland (1).
3. Connect the connecting cable to the ter-
minal base and the i/p module (6). Lead
the blue cable to the minus side and the
red cable to the plus side. Fasten the ca-
bles with terminal screws.
4. Check that the sealing hoses (7, 8) are
properly inserted on the bottom section
of the i/p module. When the module is
installed (broken line in Fig. 16), the
sealing hose including restriction and fil
-
ter must be located on the right above
the inner of the two bore holes (supply).
5. Fasten the i/p module and terminal base
using two screws each.
6. Close the housing on the side using the
cable gland (5) or a plug with sealing
ring.
7. Change model index on the nameplate
to Type 3767 i/p Positioner.
40 EB 8355-1 EN
Converting the positioner
Table 11
Required input signal
(reference variable)
Required i/p module
(order no.)
Required conversion kit
(order no.)
4 … 20 mA
0 … 20 mA
1 … 5 mA
6112-041110
6112-042110
6112-043110
1400-7574
1234
5678
Fig. 16 · Converting the positioner