5 Converting the positioner
The pneumatic positioner (3766-x...x.04
and higher) can be converted to form a
Type 3767 Electropneumatic Positioner.
Note: Conversion of explosion-protected
versions only on request.
Apart from the Type 6112 i/p Module (see
Table 11), the associated conversion kit in
-
cluding screw gland, fastening screw,
clamps and cables must be ordered.
1. Remove the support with the terminal
case (if existing).
2. Unscrew the connecting plate (3) and re-
move the silicone hose (2). Remove the
guard plate (4) and pneumatic screw
gland (1).
3. Connect the connecting cable to the ter-
minal base and the i/p module (6). Lead
the blue cable to the minus side and the
red cable to the plus side. Fasten the ca-
bles with terminal screws.
4. Check that the sealing hoses (7, 8) are
properly inserted on the bottom section
of the i/p module. When the module is
installed (broken line in Fig. 16), the
sealing hose including restriction and fil
-
ter must be located on the right above
the inner of the two bore holes (supply).
5. Fasten the i/p module and terminal base
using two screws each.
6. Close the housing on the side using the
cable gland (5) or a plug with sealing
ring.
7. Change model index on the nameplate
to Type 3767 i/p Positioner.
40 EB 8355-1 EN
Converting the positioner
Table 11
Required input signal
(reference variable)
Required i/p module
(order no.)
Required conversion kit
(order no.)
4 … 20 mA
0 … 20 mA
1 … 5 mA
6112-041110
6112-042110
6112-043110
1400-7574
1234
5678
Fig. 16 · Converting the positioner