Installation Procedure
Main power terminal block specifications
[Unit : inch(mm)]
AC power :
M4 screw
L
F1
0.51(13)
0.40(10.1)
Communication :
M4 screw
N
F2
0.67(17)
0.45(11.4)
Main power cable specifications
The power cable is not supplied with air conditioner.
Ensure the power wiring is sizing and specifications
comply with all national, state, and local codes and
regulations.
Model
Power Source RLA (A)
MOC
MCA (A) MOP (A)
Outdoor FAN1(A) FAN2(A)
AC024BXUPCH
208 - 230 V
60 Hz
17.6 1.25 - 24.1 30
AC036BXUDCH
17.8 1.25 - 24.4 35
AC036BXUPCH
17.8 1.25 1.25 25.6 35
AC048BXUPCH
23.5 1.25 1.25 32.7 40
AC060BXUPCH
23.9 1.25 1.25 33.2 40
NOTE
Outdoor units are installed using different power sources from that of indoor units, and this installation manual only
provides the MCA/MOP values for outdoor units.
For the MCA/MOP values for indoor units, refer to the installation manual for the indoor unit installed.
ŵøϑɵɇϑʪʒͱ²ŵÃߣߢߡߣߥߡʀͱͱ˝ϑϩɇʒɇθʒʀͱʒϩͱࣄÃʒͱͱθϩʪΧࢋࡠߣߧࢋߨইAࢥߩߡই࣍U9࣎ࢥߢߪࢋߥߧইAࢥߧߨই࣍Ǯ9࣎ࡡ
Outdoor temp. : 35 °C / 95 °F(DB)]
Ǥͱϩɇ˝ʪϩͱʪθɇʀʪϑߢߡࢋ
đɇуЇɇͱиɇɵʪЭͱϩɇ˝ʪɵʪϩиʪʪʪ˝ϑϑߣࢋ
Symbols
RLA: Rated Load Ampere (A)
MOC: Maximum Operating Current (A)
MCA: Minimum Circuit Ampere (A)
MOP: Maximum Overcurrent Protective Device (A)
• Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above
listed range limits.
Wire size & type must comply with the applicable local and national code.