Installation Procedure
Display contents SEG1 SEG2 SEG3 SEG4
K4 long
push
- Main micom version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit)
After short push 1 Inverter micom version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit)
After short push 2 E2P version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit)
After short push 3
Page 1 - AUTO
Page 2 - (SEG1,2 - Indoor : "A","0") (SEG3,4 - Address : ex) 00)
After short push 4
Page 1 - MANU
Page 2 - (SEG1,2 - Indoor : "A","0") (SEG3,4 - Address : ex) 00)
øͱ˝ΧЇϑ˵çߥ࣍đɇʀͱЭʪθࢋ࣎ϑ˵ͱθϩΧЇϑ˵ߢͱθʪ࣍ÃЭࢋʀͱЭʪθࢋ࣎ϑ˵ͱθϩΧЇϑ˵ߢͱθʪ࣍kߣťࢋЭʪθࢋ࣎ϑ˵ͱθϩΧЇϑ˵ߢ
ͱθʪ࣍Їϩͱɇϩʀɇʒʒθʪϑϑ࣎ϑ˵ͱθϩΧЇϑ˵ߢͱθʪ࣍đɇЇɇɇʒʒθʪϑϑ࣎ϑ˵ͱθϩΧЇϑ˵ߢͱθʪ࣍đɇʀͱЭʪθࢋ࣎ࢋࢋࢋࢋࢋࢋࢋøͱ˝
push K4 (View mode end)
7 Setting outdoor unit option switch and address manually
a Setting the option
Press and hold K2 to enter the option setting.
(Only available when the operation is stopped)
If you enter the option setting, display will show
the following.
Seg 1 and Seg 2 will display the number for
selected option.
Seg 3 and Seg 4 will display the number for set
value of the selected option.
If you have entered option setting, you can shortly
press the K1 switch to adjust the value of the Seg 1,
Seg 2 and select the desired option.
Example)
If you have selected desired option, you can shortly
press the K2 switch to adjust the value of the Seg 3,
Seg 4 and change the function for the selected option.
Example)
After selecting the function for options, press and
hold the K2 switch for 2 seconds. Edited value of
the option will be saved when entire segments
blinks and tracking mode begins.
Option
item
SEG1 SEG2 SEG3 SEG4 Function
Channel
address
00
AU
Automatic setting
(Factory default)
00~15 Manual setting
Snow
accumulation
prevention
control
01
00
Disabled (Factory
default)
0 1 Enabled
Step for
Silence mode
02
00
Disabled (Factory
default)
01 Step1
02 Step2
03 Step3
Type of
Silence mode
03
00
Automatic Silence
mode (Factory default)
0 1 Manual Silence mode
Temperature
unit
04
00 Celsius
0 1 Fahrenheit (default)