EasyManua.ls Logo

Samsung AC024BXUPCH - Current Sensor Error - (E468); DC Link Voltage Sensor Error (Short;Open) - (E469); Outdoor Unit EEPROM Read;Write Error (Option) - (E470); Outdoor Unit EEPROM Read;Write Error (H;W) - (E471)

Samsung AC024BXUPCH
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4-28 Samsung Electronics
4-2-20. Current sensor error - (E468)
Outdoor unit display
Judgment Method
Check power connection.
Check Inverter PCB.
Cause of problem
-
4-2-21. DC Link voltage sensor error (Short/Open) - (E469)
Outdoor unit display
Judgment Method
Check the value of DC Link.
Check the reactor disconnection.
Cause of problem DC Link is not normal (DC Link voltage : 264~374V)
4-2-22. Outdoor unit EEPROM Read/Write error (Option) - (E470)
Outdoor unit EEPROM Read/Write error (H/W) - (E471)
Outdoor unit display
,
Judgment Method
• Check EEPROM data
• Upload EEPROM data correspoding model name to Main PCB.
Cause of problem No or incorrect EEPROM data in the set.

Table of Contents

Related product manuals