ENGLISH-74
Setting outdoor unit option switch and key function
4. After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited value of the option will be
saved when entire segments blinks and tracking mode begins.
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
CAUTION
While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting
mode.
- If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored setting
is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress, setting will be
saved.
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency
operation for
compressor
malfunction
Individual 0 0
0 0 Disabled (Factory default)
E560 will occur when all
the compressors are set as
malfunction state.
0 1
Set compressor 1 as
malfunction state
0 2
Set compressor 2 as
malfunction state
Cooling capacity
correction
Main 0 1
0 0 7-9
Targeted evaporation
temperature [°C].
(When low temperature value is
set, discharged air temperature
of the indoor unit will decrease)
0 1 5-7 (Factory default)
0 2 9-11
0 3 10-12
0 4 11-13
0 5 12-14
0 6 13-15
Capcity correction
for heating
Main 0 2
0 0 2.8 (Factory default)
Targeted high pressure [MPa].
(When low pressure value is set,
discharged air temperature of
the indoor unit will decrease)
0 1 2.5
0 2 2.6
0 3 2.7
0 4 2.9
0 5 3.0
0 6 3.1
0 7 3.2
0 8 3.3