Installation Procedure
Step 11 Connecting the power and
communication cables
1 Before wiring work, you must turn off all power source.
2 Indoor unit power should be supplied through the breaker
(ELCB or MCCB+ELB) separated by the outdoor power.
• ELCB:Earth Leakage Circuit Breaker
• MCCB:Molded Case Circuit Breaker
• ELB:Earth Leakage Breaker
3 The power cable should be used only copper wires.
4 Connect the power cable (1(L), 2(N)) among the units
within maximum length and communication cable (F1,
F2) each.
5 Connect F3, F4(for communication) wires at the back side of the indoor unit when installing the wired remote
control.
V1F11(L) 2(N) F2
F11(L) 2(N) 1(L) 2(N)F2
F1 F2
F1 F2
F1 F2 F1 F2 N L
N L
N L N L
F1 F2 1(L) 2(N) F1 F2
F11(L) 2(N) F2F11(L) 2(N) F2 V2 F3 F4
F1 F2
F3 F4
Outdoor Unit
Indoor Unit 1
Indoor Unit 4 Indoor Unit 5 Indoor Unit 6
Indoor Unit 2 Indoor Unit 3
EEV kit
220-240 V~or
MCCB+
ELB
ELCB
Wired Remote
Control
• Ceiling, wall-mounted indoor unit.
• ELCB : Essential Installation
• The EEV Kit is optional component.
WARNING
• Power off before connecting any wires;Indoor PBA will be damaged while V1, V2, F3, F4 short each other.
• You must connect the earth cable. If earthing is not complete, electric shock or fire may occur.