EasyManua.ls Logo

Samsung AM TNVD Series - Cleaning Safety Precautions; General Cleaning Warnings; Heat Exchanger and Internal Cleaning

Samsung AM TNVD Series
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
Installation Procedure
English
Installation Procedure
You must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable
and communication cable.
Maximum length of power cables are decided within
10% of power drop. If it exceeds, you must consider
another power supplying method.
The circuit breaker (ELCB or MCCB+ELB) should be
considered more capacity if many indoor units are
connected from one breaker.
Use round pressure terminal for connections to the
power terminal block.
For wiring, use the designated power cable and connect
it firmly, then secure to prevent out-side pressure being
exerted on the terminal board.
Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
See the table below for tightening torque for the
terminal screws.
Tightening torque
N•m kgf•cm
M 3.5 0.8 ~ 1.2 8.0 ~ 12.0
M 4 1.2 ~ 1.8 12.0 ~ 18.0
Step 12 Optional: Extending the power
cable
1 Prepare the following tools.
Tools Spec Shape
Crimping pliers MH-14
Connection sleeve
(mm)
20xØ6.5 (HxOD)
Insulation tape Width 19 mm
Contraction tube
(mm)
70xØ8.0 (LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
Peel off 20 mm of cable shields from the pre-
installed tube.
CAUTION
For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
If cable wires are connected without using connecting
sleeves, their contact area becomes reduced, or
corrosion develops on the outer surfaces of the wires
(copper wires) over a long time. This may cause an
increase of resistance (reduction of passing current)
and consequently may result in a fire.
20 20 20
60
120
180
Power cable
202020
60
120
180
Pre-installed
tube for the
power cable
(Unit: mm)
DB68-08953A-00_IM_DVM QMD_EU_EN_.indd 14 2020-02-10 오후 4:23:08