Installation Procedure
Example of Installation
‐ Total power cable length L = 100(m), Running current of each units 1[A]
‐ Total 10 indoor units were installed
ELCB
10[A]
0[m] 10[m] 20[m] 100[m]
Indoor unit 1 Indoor unit 2 Indoor unit 10
9[A] 1[A]
or
MCCB+
ELB
• Apply following equation.
n
Coef × 35.6 × Lₖ × iₖ
) < 10% of input voltage [V]∑ (
1000×Ak
k=1
• Calculation
‐ Installing with 1 sort wire ‐ Installing with 2 different sort wire.
2.5 [mm²] 2.5 [mm²]
Within 198V
to 242V
······· 2.5 [mm²] ·······
-(2.2 + 2.0 + 1.8 + 1.5 + 1.3 + 1.1 + 0.9 + 0.7 + 0.4 + 0.2)= -11.2 [V]
-2.2 [V]
220 [V] 208.8 [V] : it's okay
-2.2 [V]
4.0 [mm²] 4.0 [mm²]
Within 198V
to 242V
······· 2.5 [mm²] ·······
-(1.4 + 1.2 + 1.8 + 1.5 + 1.3 + 1.1 + 0.9 + 0.7 + 0.4 + 0.2)= -10.5 [V]
-1.4 [V]
220 [V] 209.5 [V] : it's okay
-1.2 [V]
CAUTION
• Select the power cable in accordance with relevant local and national regulations.
• Wire size must comply with local and national code.
• For the power cable, use the grade of H07RN-F or H05RN-F materials.
• You should connect the power cable into the power cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 10% of supply rating among whole indoor units.
• If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over
10% of supply rating, the indoor unit is protected, stopped and the error mode indicates.
• To protect the product from water and possible shock, you should keep the power cable and the connection cord of the
indoor and outdoor units in the iron pipe.
• Connect the power cable to the auxiliary circuit breaker. An all pole disconnection from the power supply must be
incorporated in the fixed wiring (≥ 3 mm).