24
Installation Procedure
Installation Procedure
Option SEG17 SEG18 SEG19 SEG20
Explanation Buzzer control Hours of filter usage PAGE Individual control of a remote control
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
0 Use buzzer 2 1000 Hour
3
0 or 1 channel 1
1 Disuse buzzer 6 2000 Hour
2 channel 2
3 channel 3
4 channel 4
Option SEG21 SEG22 SEG23 SEG24
Explanation
Heating setting compensation / Removing
condensated water in heating mode
EEV Step of stopped unit during oil return/
defrost mode
- -
Indication
and Details
Indication
Details
Indication Details
Heating Setting
Compensation
Removing
Condensated Water
in Heating Mode
0 Default (*7) Disuse
0 Default value
1 2 °C Disuse
2 5 °C Disuse
3 Default (*7) Use (*8)
4 2 °C Use (*8)
1
Oil return or Noise
decreasing in defrost
mode
5 5 °C Use (*8)
(*1) Minimizing fan operation when thermostat is off
‐ Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
‐ Fan stops or operates Ultra low in Cooling when thermostat is off.
(*2) If external drain pump signal is used, external control (SEG14) can't be used.
(*3) It is only for wall-mounted indoor unit with EEV Integrated. If any design condition meets either of the following below,
please set SEG11 to “7”.
a The total number of wall-mounted indoor units with EEV Integrated in one (modular) system is more than 20.
b The total number of wall-mounted indoor units with EEV Integrated in one (modular) system is more than “the total of
one (modular) system’s capacity(kW) / 2” (“the total of one (modular) system’s capacity (BTU/h) / 6800”).
ex) Outdoor capacity 28kW → 28 /2 = 14. The total number of wall-mounted indoor units with EEV Integrated in one
(modular) system is more than 14.