2. Ǯ˵ʪϩ˵ʪЇϩͱΧΧʪΧɇθ˝ͱΧʪθɇϩͱѣϑ˵ʪϑࡥϩ˵ʪ˙ͱͱи˝ʒɇϩɇϑϑ˵ͱиͱϩ˵ʪͱЇϩʒͱͱθЇϩʒϑΧɇц
Result Outdoor unit display Description
Setting completed End
Setting error
E191
Indoor unit data
(displayed alternately)
Indoor unit data
SEG 1,2 = indoor unit address / SEG 3,4 = error status
ߢߢࡑđAƸΧͱθϩϑͱϩ
disabled, or a pipe is
not connected.
ߢߣࡑAͱͱ˝ͱцʒͱͱθЇϩ
is connected to MCU.
ߢߤࡑƟ˵ʪϑ˵ɇθʪʒϑʪϩϩ˝˙ͱθ
two ports is incorrect.
Example) When the MCU port connected to the indoor unit 12
is disabled, E191 and 1200 are displayed alternately
If two or more indoor units have setting errors, the data about
the next indoor unit is displayed each time you press the K2
switch.
࡛If the MCU ports to use are set incorrectly, the Auto pipe pairing operation may stop due to high-pressure
or low-pressure protection control or the data about the indoor unit that has a MCU port setting error may
be incorrect. Ensure that the MCU ports to use are set correctly.
࡛Depending on the indoor and outdoor temperatures, the Auto pipe pairing operation may stop due to
protection control.
࡛If an error occurs while the Auto pipe pairing operation is running, check the error code and take actions.
࡛Ã˙цͱЇʀɇͱϩѣϑ˵ϩ˵ʪЇϩͱΧΧʪΧɇθ˝ͱΧʪθɇϩͱɵʪʀɇЇϑʪͱ˙ϩ˵ʪΧθʪЭͱЇϑθʪɇϑͱϑࡥϑʪϩϩ˵ʪΧΧʪ
addresses manually by referring to Setting the Pipe Addresses Manually.