Capacity (kW) Ęͱ࢏
Pipe size (mm)
Liquid pipe Gas pipe
ߥߥ࢏ߨǮ (1) Ø 12.70 Ø 28.58
ߩߥ࢏ߨǮ (2) Ø 19.05 Ø 34.92
ߣߥߧ࢏ߤǮ (3) Ø 19.05 Ø 41.28
Size of the pipe connected to the outdoor unit (A)
Select the size of the main pipe according to the below table.
Outdoor unit capacity (kW)
(Cooling)
*Maximum pipe length within 90m *Maximum pipe length over 90m
Liquid pipe (mm) gas pipe (mm) Liquid pipe (mm) gas pipe (mm)
22.4 kW
Ø 9.52
Ø 19.05
Ø 12.70
Ø 22.22
ߤߤ࢏ߧǮߤߪ࢏ߣǮ Ø 22.22 Ø 25.40
note1)
ߤߪ࢏ߤǮߥߥ࢏ߨǮ
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
ߥߥ࢏ߩǮߦߢ࢏ߢǮ
ߦߢ࢏ߣǮߦߧ࢏ߢǮ
Ø 31.75
note2)
ߦߧ࢏ߣǮߧߢ࢏ߦǮ
Ø 15.88 Ø 19.05
ߧߢ࢏ߧǮߧߨ࢏ߢǮ
ߧߨ࢏ߣǮߨߥ࢏ߥǮ
ߨߥ࢏ߦǮߩߢ࢏ߥǮ
Ø 34.92 Ø 38.10
note3)
ߩߢ࢏ߦǮ߫ߪ࢏ߦǮ
Ø 19.05 Ø 22.22߫ߪ࢏ߧǮߣߥߧ࢏ߤǮ
Ø 41.28
Ø 41.28
ߣߥߧ࢏ߥǮߣߨ߫࢏ߢǮ
Ø 53.98
ߣߨ߫ߣǮߤߧߤߢǮ Ø 22.22 Ø 53.98 Ø 25.40
note1)
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe
installed on the site, a socket is provided by default together with the outdoor unit.