Refrigerant pipe installation
Refrigerant pipe installation
Basic amount of refrigerant within the outdoor unit (kg)
Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Aɇϑϑѣʀɇϩͱ
AM080JXVHGH/ET AM100JXVHGH/ET AM120JXVHGH/ET AM140JXVHGH/ET AM160JXVHGH/ET AM180JXVHGH/ET
Basic amount
6.5 6.5 6.5 9.4 9.4 8.4
Aɇϑϑѣʀɇϩͱ
AM200JXVHGH/ET AM220JXVHGH/ET AM240KXVGGH/ET AM260KXVGGH/ET
Basic amount
11.0 11.0 14.0 14.0
Aɇϑϑѣʀɇϩͱ
AM080JXVAGH/ET AM100JXVAGH/ET AM120JXVAGH/ET AM140KXVAGH/ET AM160KXVAGH/ET AM180KXVAGH/ET
Basic amount
5.5 5.5 6.5 7.7 8.4 8.4
Aɇϑϑѣʀɇϩͱ
AM200KXVAGH/ET AM220KXVAGH/ET AM240KXVAGH/ET AM260KXVAGH/ET
Basic amount
8.4 8.4 14.0 14.0
Aɇϑϑѣʀɇϩͱ
AM100MXVDGH/ET AM120MXVDGH/ET AM140MXVDGH/ET AM160MXVDGH/ET AM180MXVDGH/ET
Basic amount
5.5 6.5 7.7 8.4 8.4
Aɇϑϑѣʀɇϩͱ
AM080JXVHGR/ET AM100JXVHGR/ET AM120JXVHGR/ET AM140JXVHGR/ET AM160JXVHGR/ET AM180JXVHGR/ET
Basic amount
6.5 6.5 6.5 9.4 9.4 8.4
Aɇϑϑѣʀɇϩͱ
AM200JXVHGR/ET AM220JXVHGR/ET AM240MXVGNR/ET AM260MXVGNR/ET
Basic amount
11.0 11.0 14.0 14.0
Amount of additional refrigerant depending on the pipe size ( )
Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe ŝߨ࢏ߥߧ ŝ߫࢏ߧߤ ŝߣߤ࢏ߩߢ ŝߣߧ࢏ߪߪ ŝߣ߫࢏ߢߧ ŝߤߤ࢏ߤߤ ŝߤߧ࢏ߦߢ ŝߤߪ࢏ߧߪ
Additional amount (kg/m) 0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter
regardless of the pipe size.
Amount of additional refrigerant for each indoor unit (
)
(Unit : kg)
Capacity (kW)
Model
ߣ࢏ߧ ߣ࢏ߩ ߤ࢏ߤ ߤ࢏ߪ ߥ࢏ߤ ߥ࢏ߨ 4 ߦ࢏ߧ ߧ࢏ߨ 6 ߩ࢏ߣ ߪ ߤ 9 ߫࢏ߥ 11 ߣߣ࢏ߤ ߣߤ࢏ߪ 14 16 18 22 ߤߤ࢏ߦ 25 28 32 50
500
CMH
1000
CMH
Interior 1way cassette
(AM***HN1DEH/**)
(AM***NN1PEH/**)
0.15 0.15
Slim 1way cassette
࣑đࡒࡒࡒ࣑âࢩĘ࣒ĘߣUk²ࢩࡒࡒ࣒
0.25 0.25 0.25 0.32 0.32
2way cassette
(AM****N2DEH/**)
0.31 0.47
4way cassette S
(600x600)
(AM****NNDEH/**)
0.29 0.29 0.29 0.29 0.37 0.37 0.37
4way cassette S
(AM***F(N)N4DEH/**)
0.45 0.45 0.45 0.45 0.57 0.69 0.69
4way cassette S
(AM****N4FEH/**)
0.69 0.69 0.69 1.00 1.00 1.00 1.00 1.00 1.00
360 cassette
(AM***KN4DEH/**)
0.45 0.45 0.45 0.45 0.69 0.69 0.69
Duct S
(AM****NMPKH/**)
0.22 0.22 0.22 0.22 0.31 0.38 0.38 0.38
Duct S
(AM****NMPKH9**)
0.31 0.31 0.38 0.38 0.38
Duct S
(AM***HNHPKH/**)
0.38 0.38 0.38
Home Duct
(AM***KNLDEH/**)
0.13 0.13 0.13 0.17
Home Duct
(AM***MNLDEH/**)
0.24 0.24 0.31
Slim duct
(AM***FNLDEH/**)
0.17 0.17 0.17 0.26 0.35 0.35 0.45 0.42 0.42 0.62 0.62