Space requirement for installation
Single installation
(Unit : mm)
Height of the wall is
unlimited
Over 100 (S2)Over 500 (S1)
Over 100 Over 100
Front
side
Over 100
Over 300
<Case 1>
<Case 2>
Front side
Module installation
<Case 3>
Over 500Over 500 Over 600
Over 100 Over 100
Over 100
Over 100
Over 100 Over 100 Over 100 Over 100
Front side
Front side
<Case 1> <Case 2>
Over 200
Over 100
Over 300
(S2)
Over 500
(S1)
Over 100
Over 100
Over 100
Over 300
Over
400
Over
400
Height of
the wall is
unlimited
Front
side
Front side
For <Case 1> or <Case 3>
Height of the wall on the front side should not
be higher than 1500mm.
Height of the wall on the air inlet side should not
be higher than 500mm.
Height of the wall on the side is not limited.
If the height of the wall exceeds by certain value
(h1, h2), additional clearance [(h1)/2, (h2)/2 : Half
of the exceeded distance] should be added to
the service space (S1, S2).
1500 h1
500 h2
Front side
Air inlet side
(Unit : mm)
S1+h1/2 S2+h2/2