106
Setting the MCU and Pipe Addresses (for HR Only)
Setting the Pipe Addresses Manually
You can use the wired or wireless remote control or the S-NET Pro 2 to set the pipe addresses for each indoor unit.
Setting by using the wired or wireless remote control (For how to operate the remote
control buttons, see the remote control user manual.)
1. Turn on both the indoor unit and the remote control.
2. Enter the “Option setting mode” on the remote control.
3. Set the address of each MCU port that is connected to an indoor unit by referring to the following table.
(You can also set the address of each indoor unit.)
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Value
0
A: Address
setting mode
ߢࡑƟ˵ʪɇʒʒθʪϑϑͱ˙
the indoor unit
will not be set.
ߣࡑƟ˵ʪɇʒʒθʪϑϑͱ˙
the indoor unit
will be set.
ߢϩͱ߫ࡑ²Їʒθʪʒϑ
digit of the
indoor unit
address
ߢϩͱ߫ࡑƟʪϑʒ˝ϩ
of the indoor unit
address
ߢϩͱ߫ࡑƸϩϑʒ˝ϩ
of the indoor unit
address
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Value
10
ߢࡑƟ˵ʪŵđA
address will not
be set.
ߣࡑƟ˵ʪŵđA
address will be
set.
0
0 to F: RMC
group channel
0 to F: RMC
group address
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Value
20
ߢࡑƟ˵ʪđAƸ
address will not
be set.
ߣࡑƟ˵ʪđAƸ
address will be
set.
ߢϩͱߣࡑƟʪϑʒ˝ϩ
of the MCU
address
ߢϩͱ߫ࡑƸϩϑ
digit of the MCU
address
A to F: MCU port
address
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Value
300000
Examples> If the indoor unit whose address is not yet set is connected to port A on the MCU 1, set 0A0000-
100000-20101A-300000.
If the indoor unit whose address is set to 9 is connected to port B on the MCU 2, set 0A1009-100000-
20102B-300000.
Setting by using S-NET Pro 2
Set the pipe addresses by using Add-on > Change address on S-NET Pro 2. (For more information, see the
S-NET Pro 2 Help.)